How to Safely Shut Down a Fire Pump After Testing
news

How to Safely Shut Down an Fire Pump After Testing

2025-05-06
Share :

Fire pump testing is an essential part of maintaining a reliable fire protection system. But the job isn't done until the pump is shut down safely and properly. Improper shutdown can cause water hammer, system pressure issues, and even damage to equipment. This article outlines a clear step-by-step procedure for safely shutting down your fire pump after testing, whether electric or diesel-driven, while complying with NFPA 25 and industry best practices.

Why Proper Shutdown Matters

A safe shutdown helps:

  • Protect pump components and system valves

  • Avoid pressure surges or water hammer

  • Ensure system integrity for the next emergency

  • Meet fire safety compliance requirements


Step-by-Step: Safely Shutting Down a Fire Pump

1. Record Final Readings

Before shutdown, record the final system pressure, flow rate, and churn pressure (no-flow condition). This ensures full documentation of the test.

2. Gradually Close the Discharge Valve

Slowly close the discharge valve to prevent a sudden pressure surge or water hammer, which can damage piping and valves.

3. Stop the Pump Motor or Engine

  • For electric pumps, press the stop button or switch on the control panel.

  • For diesel pumps, follow the shutdown procedure on the controller — usually by switching the control to "Off" or "Manual Stop."

⚠️ Never stop the pump before closing the discharge valve — this can lead to backflow or system depressurization.

4. Allow System Pressure to Normalize

Wait a few minutes to monitor if system pressure stabilizes and check for any abnormal noises or leaks.

5. Reset Alarms and Controllers

Ensure all alarms triggered during testing are reset. Restore the automatic mode on both the jockey and main fire pump controllers.

6. Drain Test Lines and Remove Gauges

If temporary gauges or hoses were installed, drain and remove them properly to avoid accidental leaks or tripping hazards.

7. Log the Test and Maintenance Details

Document the entire testing and shutdown procedure in the inspection and maintenance log, as per NFPA 25 requirements.


Best Practices and Tips

  • Use a trained technician for diesel engine fire pump shutdowns.

  • Always wear PPE during testing and shutdown operations.

  • Test during non-peak hours to avoid disturbing the building’s pressure-sensitive systems.

  • Have an emergency procedure ready in case the pump fails to shut down.


Final Thoughts

A fire pump is a mission-critical asset. After every test, ensure the pump is shut down properly to keep your fire protection system ready for emergencies. By following the correct procedure, you minimize risks, extend equipment life, and ensure compliance with key standards like NFPA 20 and NFPA 25.

Get in touch with us
Rellene Su Consulta Y Nos Pondremos En Contacto Con Usted Las 24 Horas.
X
Get in touch with us
For Jiuyi Fire Technology Co., Ltd future focus on oversea market product, like the EDJ fire pump set, EJ, DJ, EEJ and so on, also include the vertica