Why Fire Pump Start Sequence Timing Is Critical?
news

Why Fire Pump Start Sequence Timing Is Critical?

2025-07-04
Share :

In any fire protection system, fire pumps serve as the lifeblood of water delivery. But while system components like pipes, sprinklers, and valves often get attention, a critical yet often overlooked element is the start sequence timing of fire pumps.

In this article, we explore why the timing of fire pump activation—especially in systems with multiple pumps or controllers—plays a crucial role in safety, system integrity, and operational reliability. We'll also review best practices for sequencing, common mistakes, and how compliance with standards like NFPA 20 ensures a safe and effective fire protection system.


1. Understanding Fire Pump Start Sequence

Start sequence timing refers to the programmed delay and order in which different fire pumps (e.g., jockey pump, electric fire pump, diesel fire pump) start during an emergency.

A typical system includes:

  • Jockey Pump – Maintains system pressure during minor leaks or pressure drops.

  • Primary Fire Pump – Kicks in when the pressure drop exceeds a threshold.

  • Secondary or Backup Pump – Activates if the primary fails or additional flow is required.

The start sequence ensures each pump turns on in the correct order, with appropriate time delays, to prevent equipment damage and ensure water delivery.


2. Why Timing Matters: Safety and System Coordination

When a fire emergency is detected, the fire pump system must respond instantly but intelligently. Improper start sequencing can result in:

  • Simultaneous pump starts causing voltage dips or generator overload.

  • Water hammer or pressure surges damaging pipelines or fittings.

  • Pump conflicts where multiple pumps run unnecessarily, reducing efficiency.

  • False system alarms or tripping of circuit breakers due to power spikes.

Correct start timing prevents these issues and ensures:

  • Smooth pressure buildup

  • Controlled electrical load

  • Reduced risk of mechanical stress

  • System reliability and longevity


3. Compliance with NFPA 20 and Other Standards

The National Fire Protection Association (NFPA) 20 standard provides detailed requirements for the installation and operation of fire pumps. It specifies that:

  • Pumps should be automatically controlled and must start upon pressure drop or manual command.

  • Each pump should have its own controller, programmed with time delays to avoid simultaneous starts.

  • Diesel and electric pumps should not start at the same time to prevent power supply overload.

UL-listed and FM-approved controllers usually include programmable delays to meet these compliance standards.


4. Start Sequence in Multi-Pump Systems

In complex facilities such as industrial plants, logistics centers, or high-rise buildings, multiple fire pumps may exist in parallel or redundant configurations. Here’s how the sequence typically works:

4.1 Jockey Pump First

The jockey pump starts first upon a slight pressure drop. It maintains pressure without activating the larger fire pumps unnecessarily.

4.2 Electric Fire Pump After Delay

If pressure continues to drop, the electric fire pump starts after a time delay (usually 5–10 seconds). This prevents premature activation due to transient drops.

4.3 Diesel Fire Pump Last

If the electric pump fails or system pressure remains low, the diesel engine-driven pump starts as a last resort, typically after 10–15 seconds more.

This hierarchy ensures controlled power usage, safety, and orderly operation.


5. Power System Coordination

When two or more pumps start simultaneously, particularly large horsepower motors, the electrical system can suffer a major voltage drop or even failure. Facilities using generators as backup power are especially vulnerable.

Proper start sequence timing helps:

  • Prevent overloading of standby generators

  • Maintain voltage stability

  • Avoid nuisance breaker tripping

  • Reduce risk of fire pump failure during actual emergencies


6. Practical Example: Industrial Warehouse

Consider a warehouse with:

  • One jockey pump (1.5 HP)

  • One electric fire pump (75 HP)

  • One diesel fire pump (100 HP)

If a pressure drop is detected:

  • The jockey pump starts immediately

  • After 5 seconds, if pressure is still low, the electric fire pump starts

  • After an additional 10 seconds, the diesel pump kicks in (only if needed)

This staggered approach prevents simultaneous current draw from the 75 HP and 100 HP pumps, protecting the power infrastructure.


7. Fire Pump Controller Settings

Modern fire pump control panels offer flexibility in timing. Common settings include:

  • Start delay: How long the controller waits before starting the pump.

  • Sequential startup: Programming multiple controllers with staggered times.

  • Manual override: Ability to start pumps manually without delay if needed.

  • Pressure thresholds: Customizable setpoints to control start sequence triggers.

Ensure each controller is properly configured and regularly tested to verify these delays are functional and effective.


8. Testing and Maintenance

NFPA 25 requires regular testing of fire pump systems. During these tests, engineers should verify:

  • Each pump starts in the correct order

  • Time delays are functional

  • Controllers operate within programmed settings

  • Power sources (utility or generator) handle load sequencing effectively

Annual flow tests, weekly churn tests, and monthly inspections are key to confirming proper operation.


9. Common Mistakes to Avoid

❌ Overlapping Timers

Failing to stagger start times can result in simultaneous startup, stressing electrical systems.

❌ Incorrect Controller Programming

Fire pump controllers must be properly configured according to system design and local code.

❌ Disabling Time Delays

Some technicians disable delay features for “faster response,” but this often creates new risks.

❌ Ignoring Generator Load Capacity

Not accounting for generator startup load when sequencing fire pumps may lead to full system failure during emergencies.


10. How to Optimize Your Fire Pump Start Sequence

  • Consult your fire protection engineer when setting or changing timers.

  • Use UL-listed controllers with programmable delays.

  • Verify compliance with NFPA 20 and local codes.

  • Perform full-system startup simulations under real-world power conditions.

  • Maintain as-built documentation for troubleshooting.

  • Keep a log of timer settings and changes during maintenance.


Conclusion

In fire protection systems, timing is everything. Proper fire pump start sequence timing ensures your system operates safely, reliably, and in compliance with global standards like NFPA 20.

Whether you're managing a high-rise building, an industrial plant, or a warehouse, sequencing your fire pumps correctly can be the difference between a controlled emergency response and catastrophic failure.

As a manufacturer of fire pumps, we strongly recommend facilities managers, consultants, and engineers prioritize start sequence programming during design, installation, and maintenance.

Need help choosing the right controller or fire pump package with smart sequencing? Contact our team at zhejiang jiuyi fire pump — we offer fully integrated, NFPA 20-compliant fire pump systems built for safety and performance.

Get in touch with us
Rellene Su Consulta Y Nos Pondremos En Contacto Con Usted Las 24 Horas.
X
Get in touch with us
For Jiuyi Fire Technology Co., Ltd future focus on oversea market product, like the EDJ fire pump set, EJ, DJ, EEJ and so on, also include the vertica