What Triggers a Fire Pump to Start Automatically?
news

What Triggers a Fire Pump to Start Automatically?

2025-07-15
Share :

In any fire protection system, the fire pump plays a critical role in ensuring adequate water pressure is available when it matters most. Whether it's installed in a commercial building, industrial facility, or logistics hub, understanding what triggers a fire pump to run is vital for engineers, facility managers, and fire safety professionals alike.

This article explores the various methods that initiate a fire pump's operation—from automatic pressure-sensing devices to manual activations—ensuring your system responds promptly and reliably during an emergency.


What Is a Fire Pump and Why It Must Start Automatically

A fire pump is a part of a fire sprinkler or standpipe system that boosts water pressure when the municipal water supply or tank pressure is insufficient. Fire pumps are typically powered by electricity or diesel engines and must be capable of starting immediately during a fire event.

The automatic operation of a fire pump ensures that human intervention is not required when seconds count. The National Fire Protection Association (NFPA 20) mandates that fire pumps must start automatically upon demand for water—usually due to a significant pressure drop caused by sprinkler or hose operation.


Primary Trigger: Pressure Drop in the Fire Protection System

The most common and critical trigger for a fire pump to run is a drop in system pressure. Here’s how it works:

1. Pressure Sensing Mechanism

Fire pumps are equipped with pressure sensing devices—typically pressure switches or transducers—located on the controller or sensing line. These devices continuously monitor system pressure.

2. Pressure Threshold

A pressure drop below a predefined threshold (setpoint) signals the controller to start the fire pump. For example, if the normal system pressure is 120 psi and the cut-in pressure is set at 105 psi, a drop below 105 psi will trigger the pump.

3. Cause of Pressure Drop

This pressure drop can occur due to:

  • Activation of a sprinkler head due to heat

  • Opening of a fire hose valve

  • Sudden system leakage or pipe burst

The moment pressure falls below the cut-in point, the fire pump controller receives a signal and initiates the pump’s start sequence.


Secondary Triggers: Manual and Remote Start Methods

Although pressure drop is the most common automatic trigger, other methods also exist to manually or remotely activate the pump when needed:

1. Manual Start at the Controller

Most fire pump control panels are equipped with a manual start button or switch. This allows personnel to start the pump directly, typically for testing or in non-pressure-related emergency scenarios.

2. Remote Manual Start

A remote start station—usually located near fire exits or hose stations—can be installed to allow manual pump initiation from a safe distance. This feature is useful if a fire is detected but has not yet triggered a sprinkler.

3. Building Management System (BMS) / SCADA

In advanced facilities, the fire pump may be integrated with the Building Management System (BMS) or a SCADA (Supervisory Control and Data Acquisition) system. These systems can send start signals based on fire alarm input, flow meter data, or visual smoke detection.


Components Involved in Fire Pump Activation

To better understand what triggers a fire pump to run, it's essential to look at the components involved in the start sequence:

1. Fire Pump Controller

The controller is the central command unit that interprets input from sensors and initiates the start process. UL-listed and NFPA 20-compliant controllers are required in most installations.

2. Pressure Switch or Transducer

Mounted on the sensing line, these devices detect changes in system pressure and send signals to the controller.

3. Jockey Pump

A jockey pump (or pressure maintenance pump) maintains system pressure under normal conditions and compensates for minor leaks. When pressure falls beyond the jockey pump’s capacity, it signals a possible fire event—prompting the fire pump to start.

4. Alarm Devices

Pressure drop or fire pump start may also trigger alarms—both local (audible and visual) and remote—to inform staff or alert the fire department, depending on the system design.
 


Sequence of Operation: Step-by-Step Example

Let’s break down a typical fire pump activation scenario:

  1. A fire starts on the second floor of a commercial building.

  2. Heat activates a sprinkler head, releasing water.

  3. System pressure drops below 105 psi.

  4. The pressure switch detects the drop and sends a signal to the fire pump controller.

  5. The controller initiates the start sequence.

  6. The fire pump starts running—drawing water from the supply and boosting pressure.

  7. The system delivers water to the active sprinkler and any connected hose stations.


Diesel Engine Fire Pumps: Additional Triggers

For diesel engine-driven fire pumps, the starting mechanism involves additional considerations:

  • The controller also monitors engine parameters (battery voltage, engine temperature, fuel level).

  • In the event of a pressure drop, the diesel engine must start within a specified time, usually within 10 seconds.

  • Diesel engines are often equipped with dual batteries and redundant starting mechanisms to ensure reliability.


Testing and Maintenance Considerations

Understanding what triggers a fire pump also highlights the importance of regular system testing and maintenance:

1. Weekly Run Tests

  • Fire pumps should be run at least once a week (per NFPA 25) to ensure readiness.

  • During these tests, pressure drops can be simulated manually to verify the automatic start.

2. Calibration of Pressure Switches

  • Pressure sensors should be calibrated to the proper cut-in and cut-out points.

  • Incorrect calibration can delay or prevent pump activation.

3. Battery and Power Supply Checks

  • For both electric and diesel pumps, backup power sources must be tested to ensure the pump starts even during a utility outage.


Common Problems That Can Prevent Fire Pump Startup

Being aware of potential issues is essential:

  • Faulty pressure switches

  • Loose wiring or control panel faults

  • Disconnected sensing lines

  • Air locks in the system

  • Depleted diesel fuel or dead batteries

A comprehensive preventive maintenance program can help prevent these failures.


Compliance with NFPA 20 Standards

NFPA 20 sets strict guidelines for the installation and performance of fire pump systems, including automatic startup procedures. Key requirements include:

  • Automatic start based on pressure drop

  • Manual and remote start capability

  • Minimum starting and run-time standards

  • Controller testing and documentation

Always verify that your fire pump system meets NFPA 20 and local code requirements.


Conclusion: Fire Pump Activation Is Critical to Fire Safety

A fire pump must be ready to start the moment it’s needed—no delays, no uncertainty. The most common trigger is a pressure drop caused by system water flow, but manual and remote options provide additional control and flexibility.

As a fire pump manufacturer, we understand how critical it is to engineer and test systems that respond precisely when lives and property are at risk. Ensuring your fire pump starts automatically and reliably requires the right components, proper installation, regular maintenance, and full code compliance.

If you’re unsure whether your fire pump system is properly configured or maintained, reach out to our technical team. We’re here to support you with expert advice and high-performance fire pump solutions.

Get in touch with us
Rellene Su Consulta Y Nos Pondremos En Contacto Con Usted Las 24 Horas.
X
Get in touch with us
For Jiuyi Fire Technology Co., Ltd future focus on oversea market product, like the EDJ fire pump set, EJ, DJ, EEJ and so on, also include the vertica